CRX4 Heat Rejection Equipment | UPS Solutions

Heat Rejection: Condensers, Dry Coolers & Cooling Towers


35 Models From 6 kW, Air Cooled, Glycol or Evaporative


✓ 35 Models Across Four Families

✓ Selected Against Your Real Design Ambient

✓ Design, Supply, Install & 24/7 Support

UPS Solutions designs, supplies and installs CRX4 outdoor heat rejection for precision cooling systems across Australia: air cooled condensers from 8 to 99 kW in single and dual circuit, condensing units with the compressor built in from 6 to 58 kW, dry coolers and free coolers from 25 to 160 kW on a glycol loop, and counterflow cooling towers from 100 to 1,000 kW. Every unit is selected against the design ambient the site actually reaches, with coastal coil coating and wet film pre-cooling available.

Since 2002 • 100,000+ UPS units supported • 24/7 support

Heat Rejection: Condensers, Dry Coolers and Cooling Towers

35 Models From 6 kW, Air Cooled, Glycol or Evaporative

Every cooling system in a building ends at the same place. Something outside has to hand the heat to the atmosphere, and this is the equipment that does it. Get it wrong and nothing upstream matters, because an indoor unit can only move as much heat as the outdoor side can get rid of.

It is also the part of the system that does the most work on the worst day. The indoor units sit in a conditioned room at a constant temperature. The outdoor equipment is out in a 40 °C Australian afternoon with the sun on it, which is exactly when the IT load is highest and the margin is thinnest. Design ambient matters more here than anywhere else in the system.

Four families cover it. Air cooled condensers for direct expansion, condensing units with the compressor already built in, dry coolers for a glycol loop, and cooling towers for evaporative rejection where the load is large enough to justify water treatment. Every one is CRX4, matched to the indoor unit and commissioned with it.

Capacities are per unit, and a plant takes as many as its load and its redundancy target call for. On a coastal site, coil coating is not an option, it is a requirement, and it is the single cheapest thing you can do to add years to the equipment.

Need heat rejection matched to a room, or an old condenser replaced?

  • Free heat load assessment
  • Design ambient checked properly
  • Coil coating for coastal sites
  • Install, commission & 24/7 support

CRX4 heat rejection at a glance

  • Published models35, from 6 kW
  • Air cooled condensers18, to 99 kW
  • Condensing units6, to 58 kW
  • Dry and free coolers6, to 160 kW
  • Cooling towers5, to 1,000 kW
  • FansEC or AC
  • RefrigerantsR410A, R32, R134a, R513A
  • Coastal coil coatingAvailable

Not sure what the indoor side needs?

Heat rejection is always specified against the unit it serves. The cooling hub walks a server room from the perimeter to the processor and shows which indoor platform belongs where, and each range page names the outdoor equipment it pairs with.

Compare every cooling position →

Four Ways to Get Rid of the Heat

What suits a site comes down to three things: what the indoor equipment needs, how much space and power there is outside, and whether water is available and worth treating.

Air cooled condensers

CRXnnAN single circuit · CRXDnnAN dual

The partner to a direct expansion indoor unit. Refrigerant arrives as hot gas, fans draw ambient air across the coil, and it leaves as liquid. No water, no treatment, nothing to maintain but the coil and the fans. The default for almost every server room.

  • Eighteen models, 8 to 99 kW
  • EC fans on the small sizes, AC above
  • Dual circuit for N+1 on one frame

Condensing units

CRXnnAC, compressor built in

The same job with the compressor already outside. That takes the noise, the vibration and most of the service work out of the room, and it suits a comms room or an office fit-out where the indoor unit needs to be as quiet and as small as possible.

  • Six models, 6 to 58 kW
  • Compressor outdoors, not in the room
  • Simplest indoor unit of the range

Dry coolers and free coolers

CRXnnnGN, glycol loop

Water and glycol are pumped out to a finned coil and cooled by ambient air. No refrigerant outdoors and no water consumed. On a cool night a free cooler can carry the load on its own and let the chiller stand down, which is where the running cost savings are.

  • Six models, 25 to 160 kW
  • EC fans, 25 percent glycol
  • Optional wet film pre-cooling for high ambient

Cooling towers

CRXnnnnTN, evaporative

Evaporating water carries far more heat than warming air does, so a tower rejects more heat in less space and gets below the dry bulb temperature. It earns its keep on a large plant, and it brings water treatment, blowdown and a maintenance regime with it.

  • Five models, 100 to 1,000 kW
  • Counterflow, inverter driven fan
  • Needs water supply and treatment

How Cold Each Method Can Get

There is a hard physical floor under every heat rejection method, and it is set by the weather rather than by the equipment. Knowing where that floor sits is most of what decides which family a site needs.

Swipe the diagram sideways to see all of it

DRY BULB the outside air WET BULB always lower Air cooled condenser Dry cooler Dry cooler, wet film Cooling tower cannot work below the outside air same floor, glycol instead of refrigerant pre-cooling moves the floor down evaporation gets below the outside air COLDER HOTTER temperature the equipment can reach
Air cooled equipment moves heat into the outside air, so it can never get the fluid below the outside air temperature, only approach it. A cooling tower evaporates water instead, and evaporation reaches down towards the wet bulb, which on a dry Australian day sits well below the dry bulb. That gap is the entire reason cooling towers exist.
The approach is what you pay for No unit reaches its floor exactly. The gap between the fluid and the ambient is the approach, and closing it takes more coil, more fan or more air. A larger condenser is not about more kilowatts on the nameplate, it is about holding capacity on the day that matters.
Free cooling lives on the left of this chart Once the ambient drops far enough below the loop temperature, a dry cooler can carry the whole load and the chiller can stand down. The warmer you design the water loop, the more hours of the year that happens, which is why chilled water design and heat rejection are one conversation.
Towers buy performance with maintenance Getting below the outside air temperature is a real advantage and it is not free. A tower brings a water supply, treatment, blowdown and a service regime, so it earns its place on a large plant rather than on a server room.

What Actually Decides the Selection

Heat rejection is where a cooling design meets the weather, the neighbours and the roof. These are the four things that settle it, and all four are cheaper to get right on paper than on site.

Design ambient, not the nameplate

Every rating is quoted at a condition, and capacity falls as the ambient air gets hotter. A unit selected on a mild design day will be short on the 42 °C afternoon when the IT load is at its highest and the room has least margin. We select against the temperature the site actually reaches, not the one that makes the datasheet look best, and that is usually the single biggest decision on this page.

Pipe run and height difference

On a split system the distance and the vertical rise between the indoor unit and the condenser both cost capacity and both have limits. A condenser on a roof five floors above the plant room is a different selection from one on a slab outside the wall. Settle the position before the equipment, because moving it afterwards means re-piping, not just re-mounting.

Redundancy outside, not just inside

An N+1 room with a single condenser is not an N+1 room. A dual circuit unit gives two independent refrigerant circuits on one frame, which is how a redundant room gets built where there is only space outside for one machine. Where there is room for two, two separate units are better again, because then the frame itself is not a single point of failure.

Noise, airflow and the neighbours

This is the only part of the system anyone outside the building ever notices. Fan selection, speed control and where the unit faces all change the noise at the boundary, and councils have opinions about it. Equally important is what the unit breathes: a condenser in a tight courtyard or under a low awning will recirculate its own hot discharge and lose capacity no matter how well it was sized.

Options That Earn Their Place Outdoors

Outdoor equipment is exposed, unattended and usually hard to get to. These are the options we specify against the site rather than against a standard build.

Coil coating for coastal and industrial sites

Salt air and industrial atmospheres attack an untreated aluminium fin, and the damage shows up as lost capacity long before it shows up as a leak. Coating costs a fraction of the unit. Anywhere near the coast it is a requirement rather than an upgrade.

EC fans and speed control

Fans that modulate instead of cycling hold head pressure steady, cut the noise at the boundary and use markedly less energy at part load, which is most of the year. On a site with a noise limit at night, fan speed control is often what makes the installation possible at all.

Wet film pre-cooling

A fine spray or wetted pad drops the air temperature entering the coil, which claws back the capacity a high ambient takes away. On a dry cooler in an Australian summer that can be the difference between holding the room and not, and it only runs on the days that need it.

Low ambient operation

Cold mornings are a problem too. Without head pressure control a condenser can drop its pressure so far that the indoor unit stops working properly, which is why a unit that is perfect in February can be unreliable in July. Specified against the site's winter minimum, not just its summer maximum.

Monitoring that reaches the BMS

Outdoor equipment is the part nobody looks at until it fails. Fan and pressure alarms brought back through the indoor unit's controller to the building management system mean a failed fan raises a ticket rather than being discovered as a room temperature alarm three hours later.

Mounting, guards and access

Anti-vibration mounts, frames for a roof or a plant deck, coil guards where hail or debris is a risk, and enough clearance around the unit for a technician to actually open it. Service access is the thing most often designed out and most expensive to design back in.

The outdoor side is where most of the running cost is decided

Indoor units sit in a conditioned space doing predictable work. The equipment outside is the part fighting the Australian ambient, and the choices made here, fan type, coil size, free cooling, pre-cooling, set the power bill for the life of the room.

See the full cooling range →

CRX4 Heat Rejection Technical Data

Thirty-five published models across four families. Figures are per unit at the rated condition, and a plant takes as many units as its load and its redundancy target call for.

Outdoor Heat Rejection

Everything here is matched to the indoor equipment it serves and commissioned with it. Capacity falls as ambient temperature rises, so the design condition is the number that matters.

Swipe the table sideways to see all of it

On a coastal site, coil coating is not optional

Salt air eats an untreated aluminium fin, and a condenser losing capacity to corrosion takes the whole room down with it on the hottest day of the year. Coating costs a fraction of the unit and is the cheapest thing you can do to add years to it. We will tell you when a site needs it.

Talk to a specialist

We Service the Brands You Already Run

The CRX4 range is vendor agnostic by design. It is built to work alongside the equipment already on your roof, and our technicians look after the major precision cooling brands whether we supplied them or not.

Outdoor equipment is the part of a cooling system that ages fastest and gets looked at least. We carry out preventive maintenance, coil cleaning, fan and motor replacement, refrigerant checks, control fault diagnosis and emergency response across Australia, New Zealand and the Pacific Islands, including on units well past their original support window.

A failing condenser very often reads as an indoor problem, because what the site sees is a room that will not hold temperature on a hot day. It is worth checking outside before replacing anything inside. Where a condenser does need replacing, a CRX4 unit can usually be matched to the existing indoor equipment rather than the whole system being torn out.

Vertiv LiebertCondensers and condensing units across the PEX, PDX and legacy Emerson range
APCOutdoor equipment across the InRow, NetworkAIR and Uniflair badged range
UniflairCondensers, dry coolers and chiller plant
StulzCyberCool and the matched outdoor range
Schneider ElectricOutdoor heat rejection across the EcoStruxure range

Running something not listed here? Send us a photo of the nameplate and we will tell you how we can help.

Talk to a cooling specialist

How a Heat Rejection Project Runs

Outdoor equipment touches the roof, the switchboard, the pipework and sometimes the council. The sequence matters, and the site visit is worth more here than on any other part of the system.

01

Assess

The indoor load, the design ambient the site actually reaches, and where there is space outside with clear air around it.

02

Design

Family, model and quantity, pipe run and rise, redundancy, fan type, coil coating and noise at the boundary.

03

Supply

CRX4 units matched to the indoor equipment and delivered with it, co-ordinated with any crane or roof access.

04

Install

Frames and anti-vibration mounts, pipework, electrical, controls, then pressure test and charge.

05

Maintain

Commission under load, then 24/7 service, with coil cleaning on a schedule that suits the site.

Step one is a site visit, not a form

Almost everything that goes wrong with heat rejection was visible on the day: a courtyard with no airflow, a roof that will not take the load, a neighbour's window ten metres away, a plant deck already full. We would rather spend an hour on site before quoting than find any of it during installation, and the heat load assessment is free.

Why Choose UPS Solutions for Heat Rejection

Australian owned critical power and cooling specialists. We design, supply, install, commission and maintain both ends of the system, indoor units and the equipment outside, as one job.

Selected against the real ambient

We size the outdoor side against the temperature your site actually reaches, the pipe run it actually has and the air it can actually breathe, not against a catalogue condition that flatters the number.

Both ends from one supplier

Indoor unit and outdoor unit specified, delivered and commissioned together, which removes the gap between trades where most commissioning problems live. One number to call when something alarms.

Australian field team

Technicians in Sydney, Melbourne, Brisbane, Perth and Adelaide, who know what a coastal site does to a coil and what a 42 degree afternoon does to a condenser.

24/7 support after handover

Coil cleaning, fan and motor replacement, refrigerant checks, control diagnosis and emergency response across Australia, New Zealand and the Pacific Islands.

A UPS Solutions technician commissioning cooling equipment on site

Send us the indoor unit and where the outdoor equipment can go

That is enough for us to select the right family and size, check the pipe run, flag anything about the position that will cost you capacity, and put a configured price in front of you.

Heat Rejection FAQs

The questions we are asked most often about the equipment outside, which is usually the part nobody thinks about until a hot day.

What is heat rejection in a cooling system?

It is the final step. A cooling system does not destroy heat, it moves it, and something outside the building has to hand it to the atmosphere. That is the condenser, dry cooler or cooling tower. An indoor unit can only ever move as much heat as the outdoor equipment can get rid of, which is why undersized heat rejection shows up as a room that will not hold temperature no matter what is done inside.

What is the difference between a condenser and a condensing unit?

A condenser is a coil and fans. The compressor sits in the indoor unit and refrigerant is piped out to the condenser to be cooled. A condensing unit has the compressor built into the outdoor cabinet, so the indoor unit becomes a coil and a fan and nothing else. That takes the compressor noise, the vibration and most of the service work out of the room, which suits a comms room or an office fit-out.

What is the difference between a dry cooler and a cooling tower?

A dry cooler passes water and glycol through a finned coil and blows ambient air across it. Nothing evaporates, nothing is consumed and there is nothing to treat, but it can never get the fluid below the outside air temperature. A cooling tower evaporates water instead, which carries far more heat and reaches down towards the wet bulb temperature, below the outside air. The tower performs better and brings water treatment, blowdown and a maintenance regime with it.

Why does my cooling struggle on hot days?

Usually because the outdoor side has run out of capacity, not the indoor unit. Every rating is quoted at a design ambient, and capacity falls as the outside air gets hotter. If a unit was selected on an optimistic design day it will be short on a 42 °C afternoon, which is exactly when the IT load is highest. A dirty coil, a failed fan or a unit recirculating its own discharge in a tight courtyard will do the same thing.

Do I need coil coating near the coast?

Yes, and it is not an upgrade, it is a requirement. Salt air corrodes an untreated aluminium fin, and the damage shows up first as lost capacity rather than as a visible leak, so it is often missed until the room has a bad day. Coating costs a fraction of the unit and adds years to it. The same applies on industrial sites with an aggressive atmosphere.

What is free cooling, and does it work in Australia?

Free cooling means running the system on ambient air alone once it is cold enough, with the chiller or compressors stood down. It works here, and how many hours a year it works depends almost entirely on how warm the water loop is designed. A loop designed to run warm reaches the free cooling threshold far more often than a cold one, which is why water temperature and heat rejection should be settled in the same conversation.

Can I replace just the condenser and keep the indoor unit?

Often, yes, and it is usually the cheaper answer. A CRX4 condenser can frequently be matched to existing indoor equipment rather than the whole system being torn out. What has to be checked first is the capacity match at the real design condition, the refrigerant, and whether the existing pipework and controls will work with the new unit. Send us a photo of both nameplates and we will tell you.

How much space does outdoor equipment need?

More than the footprint. A condenser needs clear air coming in and a clear path for hot discharge going out, and it needs enough room around it for a technician to open it and clean the coil. A unit squeezed into a courtyard or tucked under a low awning will breathe its own hot discharge and lose capacity regardless of how well it was sized, which is why we would rather see the position before quoting.

How far can the condenser be from the indoor unit?

There is a limit, and both the horizontal run and the vertical rise count against it. A longer or higher run costs capacity and changes the pipe sizing and the refrigerant charge. A condenser on a roof several floors above the plant room is a different selection from one on a slab outside the wall, so the position needs settling before the equipment is chosen rather than after.

Do you service heat rejection equipment from other manufacturers?

Yes. Coil cleaning, fan and motor replacement, refrigerant checks, control fault diagnosis and emergency response, on the major precision cooling brands as well as our own, across Australia, New Zealand and the Pacific Islands. A failing condenser very often reads as an indoor problem, so it is worth having the outdoor side checked before anything inside gets replaced.