CRX4-CRAC Room Precision Cooling | UPS Solutions

CRAC Units & Computer Room Air Conditioning

Downflow & Upflow Precision Cooling, 30 Sizes From 5.5 kW


✓ 30 Sizes, Air Cooled & Water Cooled DX

✓ Humidity Control in Both Directions

✓ Design, Supply, Install & 24/7 Support

UPS Solutions designs, supplies and installs CRX4-CRAC perimeter precision cooling for data halls, server rooms and switch rooms: air cooled direct expansion from 5.5 kW a unit across 17 sizes, water cooled from 32.5 kW a unit across 13, combined to suit the room load, in downflow or upflow, with matched CRX4 condensers on the outdoor side and humidity control in both directions.

Since 2002 • 100,000+ UPS units supported • 24/7 support

Perimeter Precision Cooling for Data Halls and Server Rooms

30 Sizes From 5.5 kW a Unit, Air Cooled and Water Cooled

A CRAC unit is a floor standing precision air conditioner that conditions a whole room rather than a rack or a row. It sits on the perimeter or in a plant area, and it holds temperature and humidity inside a tight band continuously, which is the part a comfort split system was never built to do.

The capacities below are per unit. A room is built from as many units as its heat load and its redundancy target call for, which is why there is no upper limit on what a CRX4 room can be sized to, only on what one cabinet does. Group control links up to 8 units so they share capacity and rotate standby duty between them.

In downflow it discharges into a raised floor plenum and the air rises through perforated tiles into the cold aisle. In upflow it discharges into the room or a ceiling void. Both configurations are available across the range, and CRAC is the only part of the CRX4 range that controls humidity in both directions, adding moisture as well as removing it.

Need a room sized, or an ageing CRAC replaced?

  • Free heat load assessment
  • Downflow or upflow sizing
  • Matched CRX4 heat rejection
  • Install, commission & 24/7 support
CRX4 room precision cooling units installed on the perimeter of a server room
CRX4 precision cooling unit installed in a plant room

Indoor unit

CRX4 air cooled condenser installed on an external wall

Matched condenser

Downflow, Upflow, and the Humidity Nobody Else Handles

The configuration is set by where the air has to go, not by preference. Get it wrong and the room fights itself, with supply air short circuiting back to the return instead of passing through the racks.

Downflow

Discharges down into a raised floor plenum. Air rises through perforated tiles directly in front of the racks, which is why downflow suits a contained cold aisle and a hall with a floor void to use.

Upflow

Discharges up into the room or a ceiling void, so no raised floor is required. The usual answer for comms rooms, switch rooms and retrofits into buildings that were never built as data halls.

Humidity, both directions

Electrode or ultrasonic humidification adds moisture, and the cooling coil removes it. CRAC is the only platform in the CRX4 range that does both, which matters in rooms with static sensitive equipment and in dry inland climates.

Inside a CRAC Unit

The same refrigeration loop runs in every direct expansion CRAC, and understanding where the heat actually goes is what makes the difference between a room that holds set point and one that fights itself. Step through it below.

Hot air Cooled air Refrigerant loop

Swipe the diagram sideways to see all of it

INSIDE OUTSIDE CRX4 CRAC INDOOR UNIT 1 RETURN AIR 2 FILTER 7 EXPANSION VALVE 3 EVAPORATOR 4 FAN 5 COMPRESSOR 6 CONDENSER

Stage 1

The loop runs continuously at a steady duty, and that is the real difference between precision cooling and comfort cooling. A split system is built to cycle for a room that empties at night. A CRAC is built to hold a set point every hour of the year, against equipment that never stops producing heat.

CRX4 CRAC, On Site

The CRX4 range in the environments it was built for. Precision cooling we have specified, installed and commissioned in Australian data halls, server rooms and switch rooms.

Three CRX4 CRAC perimeter precision cooling units supplied by UPS Solutions
CRX4 CRAC, the perimeter range
CRX4 precision cooling deployed in a data centre hall
Precision cooling in a data centre
CRX4 CRAC indoor cabinet with the front panel in place
CRX4 CRAC indoor cabinet
A selection of UPS Solutions critical power and cooling projects
Projects across Australia

Every installation starts with a heat load assessment and ends with the system commissioned under load. The technical data that follows is what we select from once we know what the room actually has to shift.

CRX4 CRAC Technical Data

Thirty published sizes across air cooled and water cooled direct expansion, from 5.5 kW a unit. Figures are per unit, and a room takes as many as its load needs. Every indoor unit is matched to a CRX4 condenser on the outdoor side, specified and commissioned as one system.

Room Precision Cooling, Direct Expansion

Capacity per unit at 37 °C / 24% RH return air. Sensible heat ratio 85 to 94.5 percent. Chilled water CRAH units are a separate platform, linked below.

Swipe the table sideways to see all of it

Above roughly 120 kW a unit, chilled water is the better platform

CRX4 chilled water CRAH units run to 265.8 kW at 100 percent sensible, with no refrigerant in the room and no dehumidification penalty.

Chilled water & CRAH →

What Comes Fitted, and What You Can Add

The options below are where a CRAC either earns its running cost back or does not. We specify them against the room rather than selling a standard build.

EC plug fans

Modulate airflow to the actual load rather than running flat out. Most of the energy saving on a modern CRAC is here, not in the compressor.

Inverter scroll compressors

Match capacity continuously instead of cycling on and off, which holds the room inside a tighter band and stops short cycling at low load.

Humidification and reheat

Electrode or ultrasonic humidifiers, plus electric reheat, so the unit can hold humidity as well as temperature in both directions.

G4 to F7 filtration

Standard G4, with F7 available where the room is dusty or the outside air is not clean. Easy change elements, no tools.

Controls and integration

SNMP and Modbus web card with email alarms, and group control of up to 8 units for capacity sharing and standby rotation.

Resilience options

Dual power feed, condensate pump, water leak detection, and remote temperature and humidity sensors placed where the load actually is.

Every Air Cooled CRAC Needs a Condenser

The outdoor side is CRX4 too, matched size for size to the indoor unit and commissioned with it. It is also where most of the running cost is decided, because this is the equipment fighting the Australian ambient.

Matched CRX4 Air Cooled Condensers

8 to 99 kW. Dual circuit equivalents carry a D, so CRXD52AN, CRXD62AN, CRXD76AN and CRXD85AN.

Swipe the table sideways to see all of it

ModelCapacity kWFansFan typeW x D x H mm
CRX08AN81EC800 x 420 x 790
CRX12AN121EC800 x 420 x 790
CRX18AN182EC800 x 420 x 1240
CRX24AN261AC1407 x 990 x 689
CRX32AN321AC1407 x 990 x 689
CRX38AN411AC1407 x 990 x 695
CRX42AN461AC1607 x 1273 x 695
CRX52AN581AC1607 x 1273 x 695
CRX62AN712AC1907 x 1273 x 689
CRX70AN812AC1907 x 1273 x 689
CRX76AN902AC2407 x 1273 x 695
CRX85AN992AC2407 x 1273 x 695

Supports R410A, R32, R134a and R513A. On a coastal site, specify the coil coating, an uncoated coil will not last. Size on the worst ambient the site actually sees, not an annual average.

Condensing units, dry coolers and cooling towers

The full outdoor range runs from a 6 kW condensing unit to a 1,000 kW cooling tower, including dry coolers with wet film pre-cooling for high ambient sites.

See the full cooling range →

We Service the Brands You Already Run

The CRX4 range is vendor agnostic by design. It is built to work alongside the equipment already in your room, and our technicians look after the major precision cooling brands whether we supplied them or not.

Most rooms we walk into are already running something. We carry out preventive maintenance, filter and belt changes, refrigerant checks, control fault diagnosis and emergency response across Australia, New Zealand and the Pacific Islands, including on units well past their original support window.

When a room needs more capacity, CRX4 units are specified to sit alongside what is already installed, so cooling can be extended without disturbing equipment that is still doing its job.

Vertiv LiebertPEX, PDX, PCW, CRV and XD, plus legacy Emerson and Chloride
APCInRow, NetworkAIR and the Uniflair badged range
UniflairPerimeter and in-row precision cooling
StulzCyberAir, CyberRow and CyberCool
Schneider ElectricEcoStruxure cooling and room controls

Running something not listed here? Send us a photo of the nameplate and we will tell you how we can help.

Talk to a cooling specialist

Designed, Installed and Commissioned

Precision cooling is only worth what it does on site. This is a recent Australian deployment and the sequence every CRAC project follows, from the first heat load calculation to the handover.

Twin rack mounted CRAC units commissioned on site in New South Wales

Rack Mount CRAC

Twin CRAC Commissioning

Two 12 kW rack mounted CRAC units commissioned on site. One alarmed during testing, traced to an open control signal between the indoor unit and its condenser. Repaired in place, then both units passed refrigerant, control system and mains failure testing at a 21 °C set point. Commissioning is where problems surface, which is the point of doing it properly.

New South Wales 2 × 12 kW rack mount 21 °C set point
Read the case study →

How a CRAC Project Runs

01

Assess

Load, site and design conditions, including the worst ambient the site actually sees.

02

Design

Downflow or upflow, air or water cooled, redundancy and the matched condenser.

03

Supply

CRX4 indoor units and heat rejection, delivered as one package.

04

Install

Fit off, pipework, electrical and controls.

05

Maintain

Commission under load, then 24/7 service for the life of the asset.

Why Choose UPS Solutions for CRAC Units

Australian owned critical power and cooling specialists. We design, supply, install, commission and maintain the whole system, indoor unit and condenser together.

Australian field team

Local technicians across Sydney, Melbourne, Brisbane, Perth, Adelaide and beyond. The people who commission your units are the people who come back to service them.

Indoor and outdoor, one scope

The CRAC and its condenser are specified, supplied and commissioned together as one system, so nobody is arguing about which half is underperforming.

Sized on the real heat load

We calculate the load from the IT draw, the room and the redundancy target, not from floor area, and we tell you if the answer is a different platform.

24/7 support after handover

Preventive maintenance, filter and belt service, refrigerant checks and emergency response across Australia, New Zealand and the Pacific Islands.

A UPS Solutions technician commissioning cooling equipment on site

Send us the room, the IT load and the redundancy target

That is enough for us to size the units, pick downflow or upflow, match the condenser and put a configured price in front of you.

CRAC Unit FAQs

The questions we are asked most often when sizing or replacing room precision cooling.

What is a CRAC unit?

A CRAC unit is a Computer Room Air Conditioner, a floor standing precision air conditioner built to hold a room inside a tight temperature and humidity band continuously. It differs from a comfort air conditioner in three ways: it runs 24 hours a day at a steady duty rather than cycling, it is built for sensible heat because IT equipment produces almost no moisture, and it controls humidity in both directions. The CRX4 range starts at 5.5 kW a unit across thirty sizes, and a room is built from as many units as its load needs.

What is the difference between a CRAC and a CRAH unit?

A CRAC unit has its own refrigeration circuit, so it rejects heat through a condenser or a condenser water loop. A CRAH unit has no compressor, it is a coil and fan fed with chilled water from a central plant. CRAC suits rooms up to roughly 120 kW a unit and sites with no chiller. CRAH is the better platform above that, and it is 100 percent sensible with no dehumidification penalty.

Should I choose downflow or upflow?

Downflow if you have a raised floor to discharge into, because the air then rises through perforated tiles directly in front of the racks. Upflow if you do not, because it discharges into the room or a ceiling void. Upflow is the usual answer for comms rooms, switch rooms and retrofits into buildings that were never designed as data halls. Both are available across the range.

Why can I not just use a normal split system?

Three reasons. A comfort unit is designed for people, so a large share of its capacity goes to removing moisture that IT equipment never produced, which wastes capacity you paid for. It is built to cycle rather than run continuously, so a 24 hour duty shortens its life considerably. And it cannot add humidity, so in a dry room you have no defence against static.

How do I know what capacity I need?

It comes from the IT load in kW, plus the room fabric, lighting, people and any fresh air, then a redundancy allowance on top. Floor area on its own is close to meaningless, because two rooms of identical size can differ by a factor of ten in heat load. Send us the IT draw and the room details and we will size it properly.

What does N+1 mean and do I need it?

N+1 means one more unit than the load requires, so any single unit can fail or be taken out for service without the room losing cooling. Whether you need it is a question of what an over temperature event costs you. Group control across up to 8 units handles capacity sharing and standby rotation automatically, so the spare unit is not sitting idle and ageing differently to the rest.

Can you replace an existing CRAC without shutting the room down?

Usually, and it is a common piece of work. The sequencing depends on whether you have redundancy to lean on, where the pipework runs and how the unit gets in and out of the building. Temporary cooling is sometimes needed to carry the load during the swap. It is set at design stage against your maintenance windows.

What refrigerant do CRX4 CRAC units use, and what about the phase down?

The range runs R410A, with R32, R134a and R513A available. Australia's HFC import quota steps down over the next decade, so the practical questions on an existing unit are charge size, leak detection and whether the platform can take an alternative refrigerant later. All three are worth asking before you commit to a replacement.

Do you supply the outdoor condenser as well?

Yes, and we would rather you did not buy it separately. Every CRX4 indoor unit has a matched CRX4 condenser from 8 to 99 kW, single or dual circuit, specified and commissioned together. On a coastal site, specify the coil coating, because an uncoated coil will not last.

Do you service CRAC units you did not supply?

Yes. Preventive maintenance, filter changes, refrigerant checks, control faults and emergency response, across Australia, New Zealand and the Pacific Islands, on most brands as well as our own.