CLICK HERE TO CONTACT US

UPS Solutions 60kVA/60kW 3:3/3:1/1:1 Phase Online UPS System XRT-3PH-60KVA

60kVA/60kW

Designed for high-capacity server rooms and data centre applications, the XRT 3-Phase 60KVA model is equipped with advanced features to ensure reliable and efficient power supply.

This model employs state-of-the-art technology to offer robust performance and includes a variety of features designed to optimize power delivery and safeguard essential equipment.

Input Specifications:
Voltage (Vac): 380/400/415 (138~485 L-L)
Frequency (Hz): 40~70
Power Factor: ≥0.99
Phase: 3φ4W+PE
THDi: <3% at full linear load

Bypass Specifications:
Bypass Voltage (Vac): 380/400/415
Voltage Range: -20% (-10%/-15%/-30% selectable)/+15% (10%/20%/25% selectable)
Overload: ≤130%: long run; 130%< load ≤150%: 5min; 150%< load ≤200%: 1s; 200%< load ≤300%: 100ms; >300%: OUTPUT immediately.

Output Specifications:
Capacity (kW): 60
Power Factor: 1 (0.5 leading to 0.5 lagging)
Voltage (Vac): 380/400/415±1%
Frequency (Hz): 50/60±0.1% (Battery mode)
Phase: 3φ4W+PE
Three Phase Difference: ≤1%
THDv: <1% at linear load, <4% at non-linear load
Transfer Time (ms): 0
AC-AC Efficiency: up to 96.5%
Overload: 101-105% Long run, 106-110% load for 60 minutes, 111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass

Battery Specifications:
Battery Voltage (Vdc): ±192(±168 ~±288 adjustable)
Battery Type: External
Charging Current (A): MAX 30

General Specifications:
Communication Interface: RS232, RS485, MODBUS, dry contact (BMS, SNMP, expend dry contact card are optional in slot)
Display: 4.3" Touch screen+LED+LED bar
Alarm: AC input abnormal, low battery, overload, failure
Protection: Output short-circuit, overload, over-temperature, battery low voltage, output over/low voltage
Noise (dB): <65
Altitude(m): 0-2000 no derate. 2000-3000 m derate power by 1 % per each 100 m increase
IP: IP20
Working Temperature (°C): 0 ~ 40 no derate, 40~50 auto derate.
Relative Humidity: 0 ~ 95%, no condensation
Dimension (W×D×H)(mm): 400×960×1200
Weight (kg): 145

Key Features:
• Advanced double-conversion topology for seamless power delivery
• High power factor and efficiency for energy savings
• Wide input voltage range for versatile compatibility
• Robust overload and short-circuit protection
• State-of-the-art touch screen display for easy monitoring and control
• Scalable external battery options for extended runtime
• Comprehensive communication interface support including RS232, RS485, MODBUS
• Ideal for critical applications in large server rooms and data centre's

Industry-Leading Service and Support:
• Full manufacturer's warranty and support
• Expert installation and commissioning services available
• Dedicated technical support and customer service

Download Brochure
KVA
Topology
Wiring Type

Related Items